电容器型是用于抑制真空开关或少油开关操作电容器组产生的过电压,保护电容器组免受操作过电压的损坏。
系统
标称
电压
kV
(有效值)
|
避雷器额 定 电 压 kV
(有效值)
|
避雷器持续运行电压
kV
(有效值)
|
直 流1mA参考电压
kV
(有效值)
|
2ms
方波通流容量
A
|
残 压
|
伞 径
φ
mm
|
高 度
H
mm
|
|
||
雷电冲
击电流
|
操作冲
击电流
|
|||||||||
KV (峰值) ≯
|
||||||||||
Y5WR-5/13.5
|
3
|
5
|
4.0
|
7.2
|
400
|
13.5
|
10.5
|
100
|
220
|
|
YH5WR-5/13.5
|
100
|
200
|
|
|||||||
Y5WR-10/27
|
6
|
10
|
8.0
|
14.4
|
400
|
27.0
|
21.0
|
100
|
220
|
|
YH5WR-10/27
|
100
|
200
|
|
|||||||
YH5WR-10/27DL
|
100
|
200
|
|
|||||||
Y5WR-12/32..4
|
10
|
12
|
9.6
|
17.4
|
400
|
32.4
|
25.2
|
100
|
270
|
|
YH5WR-12/32..4
|
100
|
257
|
|
|||||||
YH5WR-12/32..4DL
|
100
|
257
|
|
|||||||
Y5WR-15/40.5
|
10
|
15
|
12.0
|
21.8
|
400
|
40.5
|
31.5
|
100
|
270
|
|
YH5WR-15/40.5
|
100
|
257
|
|
|||||||
YH5WR-15/40.5DL
|
100
|
257
|
|
|||||||
Y5WR-17/45
|
10
|
17
|
13.6
|
24.0
|
400
|
45.0
|
35.0
|
100
|
270
|
|
YH5WR-17/45
|
100
|
257
|
|
|||||||
YH5WR-17/45DL
|
100
|
257
|
|
|||||||
Y5WR-51/134
|
35
|
51
|
40.8
|
73.0
|
400
|
134
|
105.0
|
232
|
1080
|
|
YH5WR-51/134
|
170
|
620
|
|
|||||||
YH5WR-51/134DL
|
110
|
620
|
|
|||||||
Y5WR-52.7/134
|
35
|
52.7
|
41
|
74.0
|
400
|
134.0
|
105.0
|
232
|
1080
|
|
YH5WR-52.7/134
|
170
|
620
|
|
|||||||
YH5WR-52.7/134DL
|
110
|
620
|
|